Active Harmonic Filter Cabinet

Composed of multiple AHF modules, HTQF C series floor-standing AHF can provide harmonic compensation current from 30A up to 600A per cabinet.



Introduction


Composed of multiple AHF modules, HTQF C series floor-standing AHF can provide harmonic compensation current from 30A up to 600A per cabinet. In addition, with highly customizable floor-standing cabinet, it can be flexible in terms of protection class and dimensions to cope with variable site conditions



Proven Performance Powered by HTQF AHF Modules


The HTQF C series floor-standing AHF takes advantage of the proven technology of HTQF AHF modules and features the same cutting-edge harmonic filtering performance.



● Voltage ratings from 230V to 690V

● 3-level IGBT inverter topology for 20kHz switching frequency 

● Dual-DSP controller in each module for real-time current tracking and dynamic compensation


● Target THDi ≤5%

● Filtering up 50th harmonics simultaneously

● Selective compensation: ON/OFF and filtering factor (amplitude) for each order can be set individually

● 5ms response time

● Dual algorithms: Fast Fourier Transformation (FFT) and Instantaneous Reactive Theory (P-Q Theory)

● Energy efficiency above 97%

● Dynamic reactive power compensation for both inductive and capacitive loads

● Load balancing function available in both 3-wire and 4-wire models

● Multiple working modes with task priority concept for multi-task applications




When One Plus One is Greater Than Two 



HTQF C series floor-standing AHF is not just the sum of individual AHF modules. Instead, it offers much more added features than AHF modules to form a complete harmonic filtering solution.


● 600A maximum for single cabinet

● Independent operation for each AHF module, one module failure won't affect other modules' operation

● Each AHF module protected by individual circuit breaker without disconnecting the whole cabinet in case of fault

● Hot-swappable module and cabinet available as option


● 7-inch multiple-language HMI as standard

● Comprehensive grid side and load side electrical parameters displayed

● Waveform and harmonic bar chart displayed

● Detailed alarms and fault messages with time stamps are stored in history page for quick troubleshooting

● USB host function used to export history events and screenshots for remote fault diagnosis

● The operating status of all modules can be monitored centrally on the HMI

● Status of major components such as IGBTs, reactors, DC link in each module displayed

● All the modules can be configured simultaneously or individually

● TCP/IP or Profibus communication available as option


● Protection class available from IP31 up to IP54

● Highly customizable cabinet to cope with all site requirements

● Dedicated ventilation fan for each AHF module for optimal airflow


● Each AHF module and the whole cabinet double checked with patented harmonic and reactive load simulator.



Specifications


General Parameters

Rated Voltage

230V (-20-+15%)

400V (-20-+15%)

480V (-20-+15%)

690V (-20-+10%)

Rated Frequency

50/60Hz±5%

Harmonic Current Rating

230V: 30-600A

400V: 30-600A

480V: 75-300A

690V: 75-300A

Wire System

4-wire or 3-wire

Performance

Inverter Topology

3-Level IGBT Inverter

Harmonics Compensation Capability

THDi<5%

Harmonic Spectrum

2nd to 50th harmonics

Selective Harmonic Compensation

2nd to 50th harmonics all can be selected individually, and the filtering degree of each order can be set individually

Response Time

Instantaneous response time (control reaction time) < 0.1ms

Full response time < 15ms

Neutral Current Compensation

3 times the RMS line current for 4-wire mode

Working Mode

Harmonic first, Reactive power first, Unbalance correction first, Reactive power only, Harmonic only, Unbalance   correction only

Targeted PF

Targeted power factor programmable from 0.6 (inductive) to 0.6 (capacitive)

Unbalance Correction Capability

To correct unbalance factor to less than 5% within capacity

Power loss

Less than 3% of rated power

Protections

Over-voltage, Undervoltage, Inverter overcurrent, Over-temperature, Overload, etc.

Anti-Resonance Patent

CN101924368A

HMI and Communication

HMI

7-inch true-color TFT touch-screen

Language

English, Spanish, Italian, Polish, Korean

Communication Interface

RS-485

Communication Protocol

MODBUS-RTU

Current Transformer (CT)

CT Requirements

3 CTs required (class 0.5 or better), Secondary rating: 5A

CTs are not included in the scope of supply.

CT Location

Supply side or load side programmable

Enclosure

Enclosure Protection Class

IP31 as standard, other protection class available upon request

Color

RAL7035 light grey

Cable Entry

Top or bottom cable entry, please specify when placing order

Installation Environment

Indoor

Mounting Method

Floor-standing

Cooling Type

Forced-air cooling

Ambient Environment

Operation Temperature

-25-40℃

Storage Temperature

-25-70℃

Humidity

Maximum 95% non-condensation

Altitude

2000m (higher operation altitude allowed with derating)

Standards

Design Standards

EN61000-6-4:2007+A1:2016,  EN61000-6-2:2017

EN50178:1997